ETC Group S.r.l.ETC GROUP S.r.l.Air Filtration Technologies

Scientific blog · Design and verification

Chimney flue after the water scrubber: condensate, 316L stainless steel, slope and terminal

Dott. Ing. Artur Cokaj ·

After washing, the flue gases leave at 45-50 °C and saturated with vapour. How to build the duct downstream of a soot scrubber: material, joints, slope, terminal, fan position and condensate.

The water-based soot scrubber changes the conditions in the duct that follows it. Before the machine, hot soot-laden flue gases pass through; after it, washed air passes, at 45-50 °C on a correctly sized wood-fired oven, saturated with vapour. The downstream duct must therefore be designed for moisture and condensate.

The scrubber treats the flue gases along their path but does not make them disappear: after the machine an exhaust duct is still required, with its position and terminal determined by the municipal building and health regulations.

Which material and which joints?

ETC specifies a sealed AISI 316L stainless steel duct, with joints and installation suitable for condensate: no liquid must escape from the joints. The choice of material must in any case be checked against the actual conditions of the installation.

Slope and route

The downstream route avoids descending sections, pockets and stagnation points. The indicative upward slope is at least 5°, so that condensate does not collect in the duct.

Which terminal to fit?

At the top the duct remains open upwards, with an open or truncated-cone terminal. ETC advises against Chinese hat caps, rotating cowls and restrictive terminals.

Where does the fan go?

When natural draught is insufficient, the fan is mounted after the scrubber. Mounted before it, it pressurises the machine and smoke escapes from inspection doors, joints and overflow. It is supported independently or on the dedicated ETC bracket, with anti-vibration mounts. The selection is made on the performance curve at the duty point, i.e. required airflow and total static pressure: motor power and free-blowing airflow are not criteria.

Fan condensate

On the stainless steel fan the condensate drain must be connected to a suitable drain or, where the configuration allows, closed so that the condensate flows back towards the scrubber. No leaks or stagnation must remain.

Inverter control

The fan speed is adjusted with a Toshiba inverter and set during commissioning. In ETC configurations with a 0-50 scale, the setting does not go below about 15, unless specifically calibrated. An excessively powerful fan does not damage the machine but can draw heat away from the oven.

Is vapour at the outlet normal?

Yes. A column of water vapour leaves the terminal, more visible with cold air or high thermal load. Residual smoke may appear grey or whitish depending on the fuel. The differences are explained in Soot, white smoke and odours.

Dott. Ing. Artur Cokaj

Researcher and designer of air treatment technologies

Inventor and holder of industrial invention patent no. 102022000000572.

Technical Manager under D.M. 37/2008, categories A, C, D, E.